Features | DM-5 Power Quality Analyzer |
Wiring connection | 1P2W, 1P3W, 3P3W, 3P4W |
Measurements and parameters | Voltage, current, frequency, active power, reactive power, apparent power, active energy, reactive energy, apparent energy, power factor (cos ø), neutral current, demand, harmonics, quality (swell/dip/interruption, transients/overvoltage, inrush current, unbalance rate), capacitance calculation for PF correction unit, flicker |
Voltage (rms) | Range: 600.0 / 1000 VAccuracy: ±0.2% + 0.2%f.s.(sine wave, 40 Hz to 70 Hz)Allowable input: 1% to 120% of each range (rms). 200% of each range (peak)Display range: 0.15% to 130 % of each rangeCrest factor: 3 or lessSampling speed of voltage transient: 24 μsInput impedance: approx. 1.67 MΩ |
Current (rms) | Accuracy: ±0.2% + 0.2%f.s. + accuracy of flex current sensor (sine wave, 40 Hz to 70 Hz)Allowable input: 1% to 110% of each range (rms). 200% of each range (peak)Display range: 0.15% to 130 % of each rangeCrest factor: 3 or lessInput impedance: approx. 100 kΩ |
Swell / dip / interruption | Range: same as Voltage (rms)Accuracy: ±1.0% of nominal voltageThreshold value: In percentage of nominal voltage value |
Power and energy | CT-53 flex current sensor (3-ch): max. 6000 kWCT-500 flex current sensor (1-ch): max. 1000 kWActive power accuracy: ±0.3% + 0.2%f.s. + accuracy of flex current sensor (PF 1, sine wave, 40 Hz to 70 Hz) Influence of power factor: ±1.0% (PF 0.5, 40 Hz to 70 Hz )Wh: 0.00000 mWh to 9999.99 TWhVAh: 0.00000 VAh to 9999.99 TVAhvarh: 0.00000 varh to 9999.99 Tvarh |
Power factor | Display range: -1.000 to 0.000 to 1.000Accuracy: ±1dgt against each calculated value (for sum: ±3dgt) |
Harmonics | Harmonics order (n): 1 to 50thInter-harmonics order (n): 1 to 50thVolts: 0.0% to 100.0%, accuracy (≥3% at 100 V nominal voltage): ±10%accuracy (<3% at 100 V nominal voltage): ±0.3% of nominal voltageaccuracy (1000 V range): ±0.2% + 0.2%f.sAmps: 0.0% to 100.0%, accuracy (≥10% to max. input range): ±10% + flex current sensoraccuracy (<10% to max. input range): ±1.0% + flex current sensorWatts: 0.0% to 100.0%, accuracy: ±0.3% + 0.2%f.s. + accuracy of flex current sensor (PF 1, sine wave, 50/60 Hz)THD: 0.0% to 100.0%, Phase angle: 0.0° to ± 180° |
Flicker | Displayed items: Pst(1min), Pst, Plt, Max Pst, Max Plt, V, time leftMeasurement method: Complied with IEC 61000-4-30 and IEC 61000-4-15 Ed.2Accuracy: Pst (max.20): ±10% according to IEC 61000-4-15 |
Unbalance | Volts: 0.00% to 100.00%, accuracy: ±0.3% at 50/60 Hz, sine wave (0.00% to 5.00% according to IEC 61000-4-030)Current: 0.00% to 100.00% |
Transient | Approx. 40.96 ksps (every 2.4 μs)Range: 50 V to 2200 VdcAccuracy: ±0.5% at 1000 Vdc |
Inrush current | Range: same as Current (rms)Accuracy: ±0.4% + 0.4%f.s. + accuracy of flex current sensorThreshold value: In percentage of the measurement range |
Capacitance | Range: 0.000 nF to 9999 F, 0.000 kvar to 999 kvar |